Description

Category Specification
Model E010GER31
Phase Single phase with ground
Capacity 10000 VA / 10000 W
INPUT
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110~300VAC ± 3 % at 50% Load, 176~300VAC ± 3 % at 100% Load
Frequency Range 46~54 Hz or 56~64 Hz
Harmonic Distortion (THDi) < 4% @100% Load, < 6% @50% Load
Power Factor ≧ 0.99 @ Full Load
OUTPUT
Output Voltage 208*/220/230/240 VAC
AC Voltage Regulation (Batt. Mode) ± 1%
Frequency Range (Synchronized Range) 4654 Hz or 5664 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦1% THD (Linear Load), ≦ 4% THD (Non-linear Load)
Transfer Time – AC Mode to Battery Mode Zero
Transfer Time – Inverter to Bypass Zero
Waveform (Batt. Mode) Pure Sinewave
Overload – AC Mode 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec
Overload – Inverter to Bypass 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec
EFFICIENCY
AC Mode 94%
Battery Mode 91%
ENVIRONMENT
Operation Humidity 20-90 % RH @ 0- 40°C (non-condensing)
Noise Level Less than 58dB @ 1 Meter
MANAGEMENT
Smart RS-232 / USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser
Standard Model
Battery Type 12 V / 9 AH
Numbers 16
Typical Recharge Time 9 Hours Recover to 90% Capacity
Charging Current (max.) 1.0 A
Charging Voltage 218.4 VDC ± 1%
Long Run Model
Battery Type Depending on Applications
Numbers 16-20**
Charging Current (max.) 4.0 A
Charging Voltage (13.65VDC x Battery Number) ± 1%
Standard Model
Dimension (D X W X H) 442 x 190 x 688 mm
Net Weight 66 kg
Long-Run Model
Dimension (D X W X H) 442 x 190 x 318 mm
Net Weight 16 kg